Product Introduction:
XBD-GDL Vertical single-suction-fire multi-stage pipeline pumping systems is the Division of the original vertical multi-stage pipeline pump under fire pump on the basis of the latest standard requirements to develop a new generation of low pressure in the XBD pipeline-fire pumping systems products . For non-delivery of water and solid particles of similar physical and chemical properties of liquid water use. Applicable to the various occasions such as residential, hotels, office buildings, commercial buildings, factories, hospitals, etc. fire water supply. Production of the Division Series XBD-GDL fire pump performance, technical requirements in line with the state promulgated the new GB6245-1998 "fire pump performance requirements and test methods," the requirements of the standard, products and equipment by the State Quality Supervision and fire detection centre tested, access Shanghai fire products recognized certificates.
Product characteristics:
1. Hydraulic model of advanced, high efficiency and performance of a wide range. 2. Vertical structure, small footprint. 3. Vibration of small, low noise, using hydraulic balance axial force, so that the smooth operation of pumps, safe and reliable. 4. Pump imports and exports at the same level axis, the same specifications and standards to facilitate pipe connection, working extremely convenient.
Type Designation:
XBD 4.2/15-80 GDL
XBD – Fire pump code
4.2 – Rated pressure (1/10MPa)
15 –Rated flow(L/S)
80 – Diameter of pump outlet and inlet (mm)
GDL – Vertical structures
Technology parameters:
Flow:0.5-45L/S;
Pressure:0.2-2.0Mpa;
Power:1.1-90KW;
Rotary speed:2900r/min;
Calibre:25-150mm;
Temperature range:≤80℃。
|